Описание
Description | -30°C | -25°C | -20°C | -15°C | -10°C | -5°C | 0°C | +5°C | ||
|---|---|---|---|---|---|---|---|---|---|---|
| 25°C | Capacity | 2130 | 2911 | 3968 | 5327 | 7014 | 9053 | 11470 | 14290 | 17540 |
| Power | 1265 | 1417 | 1578 | 1748 | 1922 | 2096 | 2269 | 2436 | 2593 | |
| Current | 2.8 | 3.0 | 3.3 | 3.6 | 3.9 | 4.2 | 4.4 | 4.7 | 4.9 | |
| MassFlow | 49.6 | 86.2 | 137.6 | 197.8 | 260.7 | 320.0 | 369.7 | 403.7 | 415.8 | |
| COP | 1.68 | 2.05 | 2.51 | 3.05 | 3.65 | 4.32 | 5.06 | 5.87 | 6.76 | |
| Efficiency | ||||||||||
| 30°C | Capacity | 1807 | 2546 | 3544 | 4829 | 6426 | 8359 | 10654 | 13338 | 16434 |
| Power | 1217 | 1385 | 1564 | 1750 | 1940 | 2130 | 2317 | 2499 | 2671 | |
| Current | 2.7 | 3.0 | 3.2 | 3.5 | 3.8 | 4.1 | 4.4 | 4.6 | 4.9 | |
| MassFlow | 34.9 | 46.5 | 78.0 | 123.1 | 175.8 | 230.0 | 279.4 | 318.2 | 340.0 | |
| COP | 1.49 | 1.84 | 2.27 | 2.76 | 3.31 | 3.92 | 4.60 | 5.34 | 6.15 | |
| Efficiency | ||||||||||
| 35°C | Capacity | 1551 | 2245 | 3184 | 4394 | 5899 | 7726 | 9899 | 12444 | 15386 |
| Power | 1197 | 1386 | 1585 | 1791 | 2000 | 2209 | 2415 | 2614 | 2804 | |
| Current | 2.7 | 2.9 | 3.2 | 3.5 | 3.8 | 4.1 | 4.4 | 4.7 | 4.9 | |
| MassFlow | 58.0 | 43.7 | 54.3 | 83.4 | 125.1 | 173.2 | 221.5 | 264.1 | 294.7 | |
| COP | 1.30 | 1.62 | 2.01 | 2.45 | 2.95 | 3.50 | 4.10 | 4.76 | 5.49 | |
| Efficiency | ||||||||||
| 40°C | Capacity | 1999 | 2877 | 4010 | 5424 | 7142 | 9192 | 11598 | 14385 | |
| Power | 1405 | 1628 | 1856 | 2088 | 2319 | 2547 | 2768 | 2978 | ||
| Current | 3.0 | 3.3 | 3.6 | 3.9 | 4.3 | 4.6 | 4.9 | 5.1 | ||
| MassFlow | 70.4 | 59.1 | 71.4 | 101.1 | 142.2 | 188.6 | 234.0 | 272.5 | ||
| COP | 1.42 | 1.77 | 2.16 | 2.60 | 3.08 | 3.61 | 4.19 | 4.83 | ||
| Efficiency | ||||||||||
| 45°C | Capacity | 2612 | 3668 | 4988 | 6598 | 8523 | 10788 | 13419 | ||
| Power | 1677 | 1932 | 2190 | 2447 | 2700 | 2946 | 3180 | |||
| Current | 3.4 | 3.7 | 4.1 | 4.4 | 4.8 | 5.1 | 5.4 | |||
| MassFlow | 85.2 | 79.6 | 96.6 | 129.8 | 173.2 | 220.7 | 266.1 | |||
| COP | 1.56 | 1.90 | 2.28 | 2.70 | 3.16 | 3.66 | 4.22 | |||
| Efficiency | ||||||||||
| 50°C | Capacity | 4581 | 6081 | 7880 | 10004 | 12478 | ||||
| Power | 2292 | 2578 | 2860 | 3133 | 3396 | |||||
| Current | 4.2 | 4.6 | 5.0 | 5.4 | 5.7 | |||||
| MassFlow | 104.0 | 128.5 | 168.0 | 216.6 | 268.2 | |||||
| COP | 2.00 | 2.36 | 2.76 | 3.19 | 3.67 | |||||
| Efficiency | ||||||||||
| 55°C | Capacity | 7254 | 9235 | 11551 | ||||||
| Power | 3012 | 3317 | 3611 | |||||||
| Current | 5.2 | 5.7 | 6.0 | |||||||
| MassFlow | 165.7 | 214.6 | 271.3 | |||||||
| COP | 2.41 | 2.78 | 3.20 | |||||||
| Efficiency | ||||||||||
| 60°C | Capacity | 10627 | ||||||||
| Power | 3811 | |||||||||
| Current | 6.3 | |||||||||
| MassFlow | 268.0 | |||||||||
| COP | 2.79 | |||||||||
| Efficiency | ||||||||||
| 65°C | Capacity | 9695 | ||||||||
| Power | 3981 | |||||||||
| Current | 6.6 | |||||||||
| MassFlow | 251.1 | |||||||||
| COP | 2.44 | |||||||||
| Efficiency |