| Description | | -30°C | -25°C | -20°C | -15°C | -10°C | -5°C | 0°C | +5°C |
|---|
| 25°C | Capacity | 3825 | 6382 | 9129 | 12312 | 16180 | 20979 | 26958 | 34364 | 43444 |
| Power | 2541 | 3049 | 3480 | 3851 | 4177 | 4474 | 4758 | 5046 | 5353 |
| Current | 8.3 | 8.5 | 8.8 | 9.1 | 9.3 | 9.6 | 9.7 | 9.9 | 9.9 |
| MassFlow | 75.9 | 126.1 | 178.2 | 237.0 | 307.6 | 395.0 | 504.2 | 640.2 | 808.0 |
| COP | 1.51 | 2.09 | 2.62 | 3.20 | 3.87 | 4.69 | 5.67 | 6.81 | 8.12 |
| Efficiency | | | | | | | | | |
| | | | | | | | | | |
| 30°C | Capacity | | | 7906 | 10884 | 14426 | 18780 | 24193 | 30913 | 39188 |
| Power | | | 3517 | 3938 | 4302 | 4627 | 4926 | 5217 | 5516 |
| Current | | | 8.8 | 9.1 | 9.4 | 9.7 | 10.0 | 10.2 | 10.3 |
| MassFlow | | | 159.9 | 216.8 | 283.4 | 364.6 | 465.5 | 590.9 | 746.0 |
| COP | | | 2.25 | 2.76 | 3.35 | 4.06 | 4.91 | 5.93 | 7.10 |
| Efficiency | | | | | | | | | |
| | | | | | | | | | |
| 35°C | Capacity | | | | 9639 | 12919 | 16891 | 21802 | 27900 | 35433 |
| Power | | | | 4039 | 4461 | 4830 | 5162 | 5475 | 5783 |
| Current | | | | 9.2 | 9.6 | 9.9 | 10.2 | 10.5 | 10.7 |
| MassFlow | | | | 199.4 | 263.3 | 339.7 | 433.5 | 549.7 | 693.4 |
| COP | | | | 2.39 | 2.90 | 3.50 | 4.22 | 5.10 | 6.13 |
| Efficiency | | | | | | | | | |
| | | | | | | | | | |
| 40°C | Capacity | | | | | 11588 | 15241 | 19714 | 25253 | 32107 |
| Power | | | | | 4624 | 5056 | 5440 | 5792 | 6127 |
| Current | | | | | 9.7 | 10.1 | 10.5 | 10.8 | 11.1 |
| MassFlow | | | | | 245.5 | 318.4 | 406.5 | 514.9 | 648.6 |
| COP | | | | | 2.51 | 3.01 | 3.62 | 4.36 | 5.24 |
| Efficiency | | | | | | | | | |
| | | | | | | | | | |
| 45°C | Capacity | | | | | | | 17856 | 22899 | 29137 |
| Power | | | | | | | 5730 | 6140 | 6521 |
| Current | | | | | | | 10.7 | 11.1 | 11.5 |
| MassFlow | | | | | | | 382.9 | 484.8 | 609.8 |
| COP | | | | | | | 3.12 | 3.73 | 4.47 |
| Efficiency | | | | | | | | | |
| | | | | | | | | | |
| 50°C | Capacity | | | | | | | | 20768 | 26453 |
| Power | | | | | | | | 6492 | 6937 |
| Current | | | | | | | | 11.5 | 11.9 |
| MassFlow | | | | | | | | 457.9 | 575.5 |
| COP | | | | | | | | 3.20 | 3.81 |
Герметичный поршневой компрессор Bristol H2BG094DBEE