Производители
Описание
Description | | -30°C | -25°C | -20°C | -15°C | -10°C | -5°C | 0°C | +5°C |
---|
25°C | Capacity | 9768 | 15032 | 21344 | 28849 | 37687 | 48000 | 59932 | 73623 | 89216 |
| Power | 6445 | 7529 | 8537 | 9432 | 10180 | 10743 | 11087 | 11175 | 10971 |
| Current | 19.9 | 20.7 | 21.7 | 22.8 | 23.7 | 24.5 | 25.1 | 25.2 | 24.8 |
| MassFlow | 194.3 | 298.0 | 418.7 | 558.5 | 719.6 | 904.1 | 1114.2 | 1352.0 | 1619.5 |
| COP | 1.52 | 2.00 | 2.50 | 3.06 | 3.70 | 4.47 | 5.41 | 6.59 | 8.13 |
| Efficiency | | | | | | | | | |
| | | | | | | | | | |
30°C | Capacity | | 13325 | 19168 | 26227 | 34642 | 44558 | 56114 | 69455 | 84721 |
| Power | | 7422 | 8510 | 9523 | 10423 | 11177 | 11746 | 12096 | 12191 |
| Current | | 20.3 | 21.3 | 22.3 | 23.4 | 24.3 | 25.0 | 25.3 | 25.3 |
| MassFlow | | 272.8 | 387.7 | 523.7 | 682.8 | 867.1 | 1078.9 | 1320.2 | 1593.2 |
| COP | | 1.80 | 2.25 | 2.75 | 3.32 | 3.99 | 4.78 | 5.74 | 6.95 |
| Efficiency | | | | | | | | | |
| | | | | | | | | | |
35°C | Capacity | | | | 23595 | 31499 | 40925 | 52018 | 64917 | 79766 |
| Power | | | | 9664 | 10704 | 11632 | 12413 | 13011 | 13391 |
| Current | | | | 22.2 | 23.3 | 24.4 | 25.3 | 25.9 | 26.1 |
| MassFlow | | | | 487.4 | 642.1 | 824.0 | 1035.2 | 1277.7 | 1553.8 |
| COP | | | | 2.44 | 2.94 | 3.52 | 4.19 | 4.99 | 5.96 |
| Efficiency | | | | | | | | | |
| | | | | | | | | | |
40°C | Capacity | | | | | 28356 | 37204 | 47742 | 60111 | 74453 |
| Power | | | | | 11002 | 12091 | 13070 | 13901 | 14550 |
| Current | | | | | 23.5 | 24.7 | 25.8 | 26.6 | 27.1 |
| MassFlow | | | | | 599.6 | 776.7 | 984.9 | 1226.4 | 1503.3 |
| COP | | | | | 2.58 | 3.08 | 3.65 | 4.32 | 5.12 |
| Efficiency | | | | | | | | | |
| | | | | | | | | | |
45°C | Capacity | | | | | | | 43388 | 55136 | 68881 |
| Power | | | | | | | 13696 | 14747 | 15651 |
| Current | | | | | | | 26.4 | 27.5 | 28.4 |
| MassFlow | | | | | | | 929.8 | 1167.9 | 1443.3 |
| COP | | | | | | | 3.17 | 3.74 | 4.40 |
| Efficiency | | | | | | | | | |
| | | | | | | | | | |
50°C | Capacity | | | | | | | | 50094 | 63152 |
| Power | | | | | | | | 15529 | 16674 |
| Current | | | | | | | | 28.5 | 29.6 |
| MassFlow | | | | | | | | 1104.2 | 1375.7 |
| COP | | | | | | | | 3.23 | 3.79 |
Герметичный поршневой компрессор Bristol H2NG204DREF